Auxiliary Switch with Butting Contacts
Product description and important technical particulars:
Application:
Can be used as Auxiliary Switch
- For HV, EHV, Off load Isolators
- For 33, 66, 110, 220, 400 and 765kv SF6 Circuit Breakers
- For 3.3, 6.6, 11, 33 and 66kv VCBs
- For controlling and signaling circuits
NO/ NC Combinations available and dimension
- LINO + 1NC – 27x43x42 mm
- 2NO + 2NC – 27x43x62 mm
- 3NO + 3NC – 27x43x82 mm
- 4NO + 4NC – 27x43x102 mm
- SNO + 5NC – 27x43x122 mm
- any special requirements other than the above can also be supplied on request.
DC breaking capacity
- 1 Amp at 220V DC
- 2 Amps at 110V DC
- 4 Amps at 48V DC
- 8 Amps at 24v DC
AC breaking capacity:
- 10Amps at 110V AC
- SAmps at 220V AC
Continuous current rating:
10Amps
L/R Ration:
20 mili seconds
Insulation Resistance:
> than 500 Mega Ohms
Movement of the operating shaft:
58° + 58° = 116°
Shaft Size
8mm dia round shaft with 38mm projection at the driving end
Specific information with respect to operation of the switch:
This is a cam operated switch with butting type of contacts. The contact rivets are made of fine grain silver and nickel.
Rotary Auxiliary Switch with Wiping Type of Contacts
Product description and important technical particulars:
Application:
Can be used as Auxiliary Switch
- For Medium Voltage off load Isolators
- For Medium Voltage SF6 Circuit Breakers
iii. For Medium Voltage VCBs
iv.For Medium and signaling circuits
NO/ NC Combinations available and dimension
- 2NO+2NC (4 packets)
- 3 NO + 3NC (6 packets)
- 4 NO + 4NC (8 packets)
- 6 NO + 6NC (12 packets)
- any special requirements other than the above can also be supplied on request.
Dimensions:
Dimension of 1 packet is 44 x 64 x 43.5 mm
Note : For switch with multi packets, add 6.5mm per packet to the dimension of 43.5mm indicated above to get the over all length of the switch
DC breaking capacity
2 Amps at 110V DC
AC breaking capacity:
- 10Amps at 110V AC
- SAmps at 220V AC
Continuous current rating:
10Amps
L/R Ration:
20 mili seconds
Insulation Resistance :
> than 500 Mega Ohms
Movement of the operating shaft:
Shaft Size
8mm Sq. shaft with 40mm projection at the driving end. If required we can supply in other shaft sizes depending on the specific requirements
Specific information with respect to operation of the switch:
This is a rotary switch in which delayed on time and delayed off time indicated as above can be given.
Trip Coil Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used as closing and Tripping low voltage Air circuit breaker and Medium Voltage Vaccum Circuit breakers
Voltage Rating
Can be supplied suitable for 110, 220 Volts DC
Wattage of the coil
230 Watts
Dimensions:
35×35 x60mm
Stroke length:
23mm
Speciality:
1. This coil is being provided with separate clip on type terminal box
2. The coil is fully enclosed inside the yoke
3. Very compact and except for the operating shaft all other parts are fully enclosed



Shunt Trip and closing coil and under voltage coil suitable for AC and DC auxiliary supply
Product description and important technical particulars:
Application:
Used as closing and Tripping low voltage Air circuit breaker and Medium Voltage Vacuum Circuit breakers
Voltage Rating
Can be supplied suitable for 24,48, 110, 220 and 380 Volts AC/DC
Wattage of the coil
This is special design where 2 coils are provided on the same bobbin.
One coil is used for launching purposes and the other coil is used for holding purposes. Launching coil will draw the power for a short while, whereas holding coil will be there in the circuit continuously.
Launching coil – 200 watts
Holding coil – 5 watts
Dimensions:
65 x50 x 80 mm
Stoke length: 21mm
Speciality:
- Since provided with PCB with electronic circuit, same assemble and be used both an DC/AC
- For under Voltage sensing and tripping, a separate coil assembly and be supplied for ratings 110, 220 & 380 Volts AC
Operating Coil Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used for closing and Tripping medium voltage SF6 circuit breakers and Vacuum circuit breakers.
Voltage Rating
Can be supplied suitable for 24, 48, 110, 220 and 380 Volts DC
Wattage of the coil
500 Watts
Dimensions:
48 x 50x 100 mm
Stroke length:
25 mm
Pull Force:
Upto 13 kg (Approx)
Speciality:
If required it can be provided with clip on type terminals or wires with pin type lug.
Plug and Socket with 11 Contacts
Product description and important technical particulars:
Application: Used as draw out carriage assembly and fixed portion of the draw out carriage to have the continuity of the auxiliary circuits even in test position of the carriage.
Voltage Rating
Can be upto 500 Volts AC/DC
Continuous current carrying capacity
10 Amps AC/DC
Length of contacts:
55mm
Dimensions:
98 x66 x 74mm



Closing Magnet (solenoid) Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used as closing coil on EHV SF6 circuit breakers
Voltage Rating
Can be supplied suitable for 110, 220 and 250 Volts DC
Wattage of the coil
300 Watts
Dimensions:
105 x 70x 130 mm
Stroke length:
3mm
Max. Pull Force:
60 Kgs (Approx)
Speciality:
- This coil is being provided with separate clip on type terminals
- The coil is fully enclosed inside the yoke
- Except for the operating shaft all other parts are fully enclosed
Fast Trip Coil Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used for Indication / Signaling and actuating of associated PLC Circuits
Voltage Rating
Can be supplied suitable for 220 Volts DC
Wattage of the coil
20 Watts (Approx)
Dimensions:
35x35x30mm
Stroke length:
30mm
Release Magnet (Solenoid) Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used as Release / Trip coil on EHV SF6 circuit breakers
Voltage Rating
Can be supplied suitable for 110, 220 and 250 Volts DC
Wattage of the coil
100 Watts
Dimensions:
105 x 75x 86mm
Stroke length:
5mm
Max. Pull Force:
20 Kgs (Approx)
Speciality:
- This coil is being provided with separate clip on type terminals
- The coil is fully enclosed inside the yoke
- Except for the operating shaft all other parts are fully enclosed


Trip Coil Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used as closing and Tripping low voltage appliances like Air circuit breaker and any signaling circuits
Voltage Rating
Can be supplied suitable for 24, 30, 48, 110 and 220 Volts DC
Wattage of the coil
80 Watts
Dimensions:
44 x 48 x56mm
Stroke length:
25mm
Speciality:
The yoke is powder coated and provided with threaded holes for mounting.
Release Coil Suitable for DC Auxiliary Supply
Product description and important technical particulars:
Application:
Used as closing Tripping low voltage Air circuit breaker and any signaling circuits.
Voltage Rating
Can be supplied suitable for 24, 30, 48, 110 and 220 Volts DC
Wattage of the coil
55 Watts (Tripping) 80 watts (closing coil)
Dimensions:
33 x 39 x 73mm (Trip Coil) 44 x 48 x 56mm (closing coil)
Stroke length:
15mm (Trip coil) 25mm (closing coil)
Speciality:
The yoke is powder coated and provided with threaded holes for mounting.